Isolation Transformer

20 kVA Three-Phase Isolation Transformer

Three-phase 20 kVA isolation transformer providing complete galvanic isolation for sensitive industrial equipment. Features low leakage inductance and excellent EMI suppression.

Rating20 kVA
Voltage415V AC, 3-Phase
Coolingboth air and oil cooled
Lead Time3–4 weeks

Ref. ISO-20-3PH · Lead time 3–4 weeks · Made to order from Hapur

See full engineering specification & variants
20 kVA Three-Phase Isolation Transformer

Key Features

1:1 galvanic isolation sized for one machine plus ancillaries, with VFD-inrush margin
Three-phase balanced design
±2% voltage regulation
Shielded windings for EMI/RFI suppression
Low leakage inductance
Oil-filled construction
Flexible mounting for a machine-side or panel install

Recommended For

Single CNC machining centres with drives
Laser cutters / EDM machines with chillers
Medical imaging consoles (CT/MR gantry supply)
Precision manufacturing cells
Industrial testing equipment
Sensitive electronic systems

Specifications

SpecificationValue
Capacity20 kVA
Primary Voltage415V, 3-Phase
Secondary Voltage415V, 3-Phase
Frequency50/60 Hz
Voltage Regulation±2%
Coolingboth air and oil cooled
Weight420 kg
Warranty3 years

Reading the specification

What these numbers mean for your installation

A datasheet tells you what the unit does. This is what each figure changes about how you specify, feed and site it — worked out for the 20 kVA specifically, not the range in general.

Rated current

28 A per phase

20 kVA at 415 V three-phase is about 28 A. Isolation transformers are sized on connected load, not on the diversified figure — total the nameplate rating of everything downstream rather than a metered average.

Regulation

±2%

±2% describes how far output sags between no load and full load. It is not voltage correction: an isolation transformer passes incoming fluctuation straight through. If your supply itself is unstable, this belongs downstream of a servo stabilizer, not instead of one.

Isolation grade

Standard 1:1 galvanic

A 1:1 galvanic barrier breaks the conductive path between supply and load, giving you a separately derived neutral and a clean local earth reference. That solves earth-loop and leakage-trip problems; it is not primarily a noise-filtering device.

Sizing Guide

When is 20 kVA the right choice?

20 kVA three-phase is the smallest rating that suits machine-level isolation. A single CNC machining centre with its drives and control transformer sits between 8 and 15 kVA; a laser cutter or EDM with its chiller lands in the same band. This rating covers one machine plus ancillaries with margin for the inrush that VFD-driven spindles produce at startup. It is also the standard choice for a medical imaging room — a CT or MR console and gantry supply, where a separately derived neutral is a code requirement rather than an optimisation. Above two machines, or where a shared bus feeds several drives, step to 50 kVA.

Before you order

Where 20 kVA goes in, and what the site needs

Typical installations

We supply 20 kVA most often into single cnc machining centres with drives, laser cutters / edm machines with chillers, medical imaging consoles (ct/mr gantry supply) and precision manufacturing cells, alongside industrial testing equipment and sensitive electronic systems. What separates those sites is the sensitivity of what sits downstream, not the kVA. The same rating protects a production machine and a metrology bench, but the earthing arrangement and shield termination that each needs are not the same, and getting that wrong wastes the transformer.

Site preparation

At 420 kg you need a pallet truck at minimum and a level, load-spreading base. Check the route for ramp gradients — a hydraulic truck carrying 420 kg will not climb much of one. Leave working clearance on the terminal side for cable entry and inspection. Sustained ambient above 45 °C, or an enclosed room without cross-ventilation, requires derating — send us the room conditions and we will confirm the rating still holds where you intend to put it.