Isolation Transformer

10 kVA Single-Phase Isolation Transformer

Single-phase 10 kVA isolation transformer providing complete galvanic isolation between input and output. Ideal for protecting sensitive laboratory equipment, medical devices, and electronic test systems.

Rating10 kVA
Voltage230V Single-Phase
Coolingboth air and oil cooled
Lead Time2–3 weeks

Ref. ISO-10-1PH · Lead time 2–3 weeks · Made to order from Hapur

See full engineering specification & variants
10 kVA Single-Phase Isolation Transformer

Key Features

1:1 galvanic isolation with a clean, separately derived earth
Delivers ~43A at 230V — headroom for one instrument or a small bench of them
Shielded windings suppress EMI/RFI before it reaches the load
±2% voltage regulation
Low leakage inductance
Oil-filled construction, compact enough for a bench or rack install
Thermal overload protection

Recommended For

HPLC / GC analytical benches
Dental & ophthalmic imaging units
Broadcast & mastering audio racks
Calibration laboratories
Single sensitive instruments on a shared lab circuit
Electronic test benches

Specifications

SpecificationValue
Capacity10 kVA
Primary Voltage230V, Single-Phase
Secondary Voltage230V, Single-Phase
Frequency50/60 Hz
Voltage Regulation±2%
Coolingboth air and oil cooled
Weight180 kg
Warranty3 years

Reading the specification

What these numbers mean for your installation

A datasheet tells you what the unit does. This is what each figure changes about how you specify, feed and site it — worked out for the 10 kVA specifically, not the range in general.

Rated current

43 A

10 kVA at 230 V single-phase is about 43 A. Isolation transformers are sized on connected load, not on the diversified figure — total the nameplate rating of everything downstream rather than a metered average.

Regulation

±2%

±2% describes how far output sags between no load and full load. It is not voltage correction: an isolation transformer passes incoming fluctuation straight through. If your supply itself is unstable, this belongs downstream of a servo stabilizer, not instead of one.

Isolation grade

Standard 1:1 galvanic

A 1:1 galvanic barrier breaks the conductive path between supply and load, giving you a separately derived neutral and a clean local earth reference. That solves earth-loop and leakage-trip problems; it is not primarily a noise-filtering device.

Sizing Guide

When is 10 kVA the right choice?

10 kVA single-phase is an equipment-level isolation rating, not a plant-level one. It suits one sensitive instrument or a small bench of them — an HPLC or GC set, a dental or ophthalmic imaging unit, a mastering or broadcast rack, a calibration bench. At 230 V it delivers about 43 A, comfortably more than any single laboratory instrument draws; the rating is normally chosen for headroom and for the clean separately derived earth it provides, not because the connected load demands it. If you are isolating a whole laboratory rather than one bench, start at the 20 kVA three-phase unit instead — paralleling single-phase units across three phases creates the imbalance you were trying to avoid.

Before you order

Where 10 kVA goes in, and what the site needs

Typical installations

We supply 10 kVA most often into hplc / gc analytical benches, dental & ophthalmic imaging units, broadcast & mastering audio racks and calibration laboratories, alongside single sensitive instruments on a shared lab circuit and electronic test benches. What separates those sites is the sensitivity of what sits downstream, not the kVA. The same rating protects a production machine and a metrology bench, but the earthing arrangement and shield termination that each needs are not the same, and getting that wrong wastes the transformer.

Site preparation

At 180 kg two people and a pallet truck will position this. The practical constraint is the doorway and any step or threshold on the route, not the weight itself. Leave working clearance on the terminal side for cable entry and inspection. Sustained ambient above 45 °C, or an enclosed room without cross-ventilation, requires derating — send us the room conditions and we will confirm the rating still holds where you intend to put it.