APFC Panel

50 kVAr APFC Panel

Our 50 kVAr APFC panel automatically corrects power factor in medium-sized industrial facilities. Features microprocessor-based controller with real-time PF monitoring and automatic capacitor bank switching.

Rating50 kVAr
Voltage415V AC, 3-Phase
Coolingboth air and oil cooled
Lead Time3–4 weeks

Ref. APFC-50-3PH · Lead time 3–4 weeks · Made to order from Hapur

See full engineering specification & variants
50 kVAr APFC Panel

Key Features

Corrects PF from ~0.78 to 0.96+ on a sub-100 kVA sanctioned load
Microprocessor controller with LCD readout of live PF and kVAr
Capacitor duty-cycling spreads switching wear evenly across the bank
Mechanically interlocked contactors — no two steps can close against each other
Thermal overload protection on the capacitor bank
Basic harmonic filtering for light VFD/drive presence
Payback typically inside 8–14 months on a surcharge bill

Recommended For

Garment & textile units (motor-heavy sewing/weaving lines)
Facilities under 100 kVA sanctioned load with a low-PF surcharge
Small industrial & light engineering units
Educational institution electrical rooms
Commercial buildings with central AC plant
Hospitals (non-critical load side)

Specifications

SpecificationValue
Rated Capacity50 kVAr
Input Voltage415V ±10%
Frequency50/60 Hz
Target Power Factor> 0.95
Capacitor BankMicrofarad rating optimized
Response Time< 5 seconds per step
Weight280 kg
Warranty2 years

Reading the specification

What these numbers mean for your installation

A datasheet tells you what the unit does. This is what each figure changes about how you specify, feed and site it — worked out for the 50 kVAr specifically, not the range in general.

Correction capacity

50 kVAr

50 kVAr of switched capacitance. As a working rule, a plant running at 0.85 power factor needs roughly 0.62 kVAr per kW of load to reach 0.99 — so this bank suits a connected load in the region of 81 kW. Send us a month of billing data and we will size it against your actual demand rather than a rule of thumb.

Target power factor

> 0.95

Most Indian DISCOMs levy a penalty below 0.90 and pay an incentive above 0.95. Holding > 0.95 is usually where the payback sits — pushing closer to unity costs disproportionately more capacitance for a smaller tariff gain, and risks leading power factor at light load.

Step response

< 5 seconds per step

Capacitors switch in discrete steps at < 5 seconds per step. That is appropriate for the slowly varying reactive demand of general plant. Rapidly cycling loads — welding sets, large press lines — need a thyristor-switched or hybrid bank instead, or the contactors will wear out prematurely.

Sizing Guide

When is 50 kVAr the right choice?

50 kVAr suits facilities where the utility bill shows a power factor between 0.75 and 0.85 and the sanctioned load is below 100 kVA. A typical scenario: a garment factory running 30–40 industrial sewing machines with motors, plus tube-light banks and a central AC — the inductive load from the motors drops PF to around 0.78, triggering monthly penalty charges. A 50 kVAr APFC panel brings that to 0.96+, eliminating the penalty and reducing the apparent kVA drawn from the feeder. The payback period is typically 8–14 months. If your electricity bill shows a 'low PF surcharge' line item every month and your connected motor load is under 75 kW, this is the correct panel size.

Before you order

Where 50 kVAr goes in, and what the site needs

Typical installations

We supply 50 kVAr most often into garment & textile units (motor-heavy sewing/weaving lines), facilities under 100 kva sanctioned load with a low-pf surcharge, small industrial & light engineering units and educational institution electrical rooms, alongside commercial buildings with central ac plant and hospitals (non-critical load side). What separates those sites is how the outgoing ways get allocated. Two boards of this rating can look identical on the schedule and behave completely differently depending on whether one feeder carries most of the load or the demand is spread evenly across them.

Site preparation

At 280 kg two people and a pallet truck will position this. The practical constraint is the doorway and any step or threshold on the route, not the weight itself. Leave working clearance on the terminal side for cable entry and inspection. Sustained ambient above 45 °C, or an enclosed room without cross-ventilation, requires derating — send us the room conditions and we will confirm the rating still holds where you intend to put it.

Adjacent ratings

If 50 kVAr is not the right size

Sizing rarely lands exactly on a catalogue rating first time. These are the ratings either side of it in the same range — compare the specification before you commit.

Engineering detail on this configuration

The apfc panel pages carry the full design rationale, comparison tables and application notes behind this SKU.

Ready to specify?

Share your load profile. Get a firm proposal in 24 hours.

Send us your kVA requirement, supply voltage range, and site conditions. Our engineer will confirm whether this configuration is correct for your installation, or specify an alternative if needed. No distributors — direct from our factory in Hapur.

Submit load requirements