APFC Panel

100 kVAr APFC Panel

Our 100 kVAr APFC Panel provides efficient power factor correction for large industrial installations. Microprocessor-controlled with advanced harmonic filtering and multi-step capacitor switching.

Rating100 kVAr
Voltage415V AC, 3-Phase
Coolingboth air and oil cooled
Lead Time3–4 weeks

Ref. APFC-100-3PH · Lead time 3–4 weeks · Made to order from Hapur

See full engineering specification & variants
100 kVAr APFC Panel

Key Features

Automatic power factor correction
Target PF > 0.95
Microprocessor-based controller
8-step capacitor switching
Harmonic filtering (THD < 5%)
Real-time reactive power monitoring
Integrated thermal protection
IP54 enclosure

Recommended For

Medium Manufacturing Units
Industrial Facilities
Commercial Complexes
Hospitals with Backup Power
Shopping Centers
Industrial Parks

Specifications

SpecificationValue
Rated Capacity100 kVAr
Input Voltage415V ±10%
Frequency50/60 Hz
Target Power Factor> 0.95
Capacitor Steps8 steps
Response Time< 5 seconds per step
Weight650 kg
Warranty2 years

Reading the specification

What these numbers mean for your installation

A datasheet tells you what the unit does. This is what each figure changes about how you specify, feed and site it — worked out for the 100 kVAr specifically, not the range in general.

Correction capacity

100 kVAr

100 kVAr of switched capacitance. As a working rule, a plant running at 0.85 power factor needs roughly 0.62 kVAr per kW of load to reach 0.99 — so this bank suits a connected load in the region of 161 kW. Send us a month of billing data and we will size it against your actual demand rather than a rule of thumb.

Target power factor

> 0.95

Most Indian DISCOMs levy a penalty below 0.90 and pay an incentive above 0.95. Holding > 0.95 is usually where the payback sits — pushing closer to unity costs disproportionately more capacitance for a smaller tariff gain, and risks leading power factor at light load.

Step response

< 5 seconds per step

Capacitors switch in discrete steps at < 5 seconds per step. That is appropriate for the slowly varying reactive demand of general plant. Rapidly cycling loads — welding sets, large press lines — need a thyristor-switched or hybrid bank instead, or the contactors will wear out prematurely.

Sizing Guide

When is 100 kVAr the right choice?

100 kVAr is the most common panel size for medium-to-large factories where the electricity bill consistently shows a power factor between 0.80 and 0.88. A food processing plant running belt conveyors, pumps, and refrigeration compressors, or a pharmaceutical packaging line with several 15–30 kW servo motors, will typically have a reactive demand in the 80–120 kVAr range. This panel's 8-step switching means the controller can fine-tune compensation to within 12.5 kVAr of the target — precise enough to hold PF above 0.95 across the full production shift without overshooting. If your DG set trips on overload during grid outages, improving PF with this panel will often eliminate the issue without buying a larger DG.

Before you order

Where 100 kVAr goes in, and what the site needs

Typical installations

We supply 100 kVAr most often into medium manufacturing units, industrial facilities, commercial complexes and hospitals with backup power, alongside shopping centers and industrial parks. What separates those sites is how the outgoing ways get allocated. Two boards of this rating can look identical on the schedule and behave completely differently depending on whether one feeder carries most of the load or the demand is spread evenly across them.

Site preparation

At 650 kg you need a pallet truck at minimum and a level, load-spreading base. Check the route for ramp gradients — a hydraulic truck carrying 650 kg will not climb much of one. Leave working clearance on the terminal side for cable entry and inspection. Sustained ambient above 45 °C, or an enclosed room without cross-ventilation, requires derating — send us the room conditions and we will confirm the rating still holds where you intend to put it.

Adjacent ratings

If 100 kVAr is not the right size

Sizing rarely lands exactly on a catalogue rating first time. These are the ratings either side of it in the same range — compare the specification before you commit.

Engineering detail on this configuration

The apfc panel pages carry the full design rationale, comparison tables and application notes behind this SKU.

Ready to specify?

Share your load profile. Get a firm proposal in 24 hours.

Send us your kVA requirement, supply voltage range, and site conditions. Our engineer will confirm whether this configuration is correct for your installation, or specify an alternative if needed. No distributors — direct from our factory in Hapur.

Submit load requirements