Servo Voltage Stabilizer

75 kVA Servo Voltage Stabilizer

The 75 kVA Servo Voltage Stabilizer bridges entry-level and mid-range operations. Perfect for growing businesses needing reliable power conditioning as they scale.

Rating75 kVA
Voltage415V AC, 3-Phase
Coolingair cooled
Lead Time1 week

Ref. SVS-75-3PH · Lead time 1 week · Made to order from Hapur

See full engineering specification & variants
75 kVA Servo Voltage Stabilizer

Key Features

±1% voltage regulation accuracy
Servo motor precision control
Response time < 20 ms
Overload capacity up to 125% for 1 hour
IP54 enclosure rating
Advanced protection systems
LED status indicators
Easy installation and maintenance

Recommended For

Small to Medium Manufacturing
Food Processing Plants
Diagnostic Centers
Industrial Training Centers
Light Assembly Operations
Precision Workshops

Specifications

SpecificationValue
Capacity75 kVA
Input Voltage300V–470V, 3-Phase
Output Voltage415V ±1%
Frequency50/60 Hz
Response Time< 20 ms
Cooling Methodair cooled
Weight325 kg
Warranty3 years

Reading the specification

What these numbers mean for your installation

A datasheet tells you what the unit does. This is what each figure changes about how you specify, feed and site it — worked out for the 75 kVA specifically, not the range in general.

Rated current

104 A per phase

At 415 V three-phase, 75 kVA works out at roughly 104 A per phase. Terminate this into the stabilizer's own cable chamber via a gland plate. Check the plate is drilled for your cable diameter before delivery, and size the upstream breaker at 130 A so the protection device is never the limiting element in the feed.

Correction window

300V–470V

The unit holds output at 415V ±1% anywhere between 300 V and 470 V in. Pulling a 300 V supply back up to 415 V means adding 115 V — a 38% lift on the incoming supply, with the series winding carrying roughly 21 kVA of the 75 kVA throughput. Below 300 V it runs out of range, and the answer is a wider-window build, not more kVA.

Response time

< 20 ms

< 20 ms matters more than the ±1% accuracy figure for most buyers. The failure that actually costs you is a drive faulting on undervoltage when a large motor elsewhere on the feeder starts, and correction inside < 20 ms is what prevents it.

Overload headroom

125% for 1 hour

Direct-on-line starting draws six to eight times full-load current for a few seconds, and 125% for 1 hour is the margin that absorbs it. Keep steady-state load below about 80% of 75 kVA so this headroom is still available when the largest motor starts.

Sizing Guide

When is 75 kVA the right choice?

75 kVA is the sweet spot for a small food processing unit — one 30 kW boiler, a 15 kW blending line, conveyors, and packaging automation together draw roughly 60–70 kVA. It is also the standard choice for diagnostic centres with MRI prep rooms (not the MRI itself, which needs its own dedicated unit) and small sheet metal fabrication shops with a press brake, guillotine shear, and spot welder running on the same feeder. At 75 kVA, you are at the upper limit of reliable air-cooled performance — this unit runs air-cooled, but if ambient temperatures exceed 45°C in your electrical room, specify the oil-cooled variant.

Before you order

Where 75 kVA goes in, and what the site needs

Typical installations

We supply 75 kVA most often into small to medium manufacturing, food processing plants, diagnostic centers and industrial training centers, alongside light assembly operations and precision workshops. What separates those sites is duty cycle rather than load. A rating that runs cool on single-shift work sits near the top of its thermal range on a continuous three-shift line, and that is the point at which oil cooling stops being optional.

Site preparation

At 325 kg you need a pallet truck at minimum and a level, load-spreading base. Check the route for ramp gradients — a hydraulic truck carrying 325 kg will not climb much of one. Leave working clearance on the terminal side for cable entry and inspection. Sustained ambient above 45 °C, or an enclosed room without cross-ventilation, requires derating — send us the room conditions and we will confirm the rating still holds where you intend to put it.

Ready to specify?

Share your load profile. Get a firm proposal in 24 hours.

Send us your kVA requirement, supply voltage range, and site conditions. Our engineer will confirm whether this configuration is correct for your installation, or specify an alternative if needed. No distributors — direct from our factory in Hapur.

Submit load requirements