Servo Voltage Stabilizer

300 kVA Servo Voltage Stabilizer

Our 300 kVA Servo Voltage Stabilizer is engineered for enterprise-level power stability. Features advanced servo-motor technology with robust design for continuous operation in demanding industrial environments.

Rating300 kVA
Voltage415V AC, 3-Phase
Coolingboth air and oil cooled
Lead Time2 weeks

Ref. SVS-300-3PH · Lead time 2 weeks · Made to order from Hapur

See full engineering specification & variants
300 kVA Servo Voltage Stabilizer

Key Features

±1% voltage regulation accuracy
Servo motor-based automatic voltage control
Response time < 20 ms
Overload capacity up to 150% for 30 minutes
ONAN cooling (natural air circulation)
IP54 enclosure
Advanced protection: overload, overvoltage, phase failure
Pure copper coil for efficiency

Recommended For

Large Manufacturing Facilities
Steel Mills
Automotive Manufacturing
Textile Mills
Paper Manufacturing
Power Distribution Substations

Specifications

SpecificationValue
Capacity300 kVA
Input Voltage300V–470V, 3-Phase
Output Voltage415V ±1%
Frequency50/60 Hz
Response Time< 20 ms
Cooling Methodboth air and oil cooled
Weight1200 kg
Warranty3 years

Reading the specification

What these numbers mean for your installation

A datasheet tells you what the unit does. This is what each figure changes about how you specify, feed and site it — worked out for the 300 kVA specifically, not the range in general.

Rated current

417 A per phase

At 415 V three-phase, 300 kVA works out at roughly 417 A per phase. At 417 A you are normally into parallel cable runs per phase rather than a single conductor. Confirm the terminal chamber accepts the number of runs your cable schedule calls for — discovering it does not, on the day of commissioning, is the most common reason installations at this rating slip.

Correction window

300V–470V

The unit holds output at 415V ±1% anywhere between 300 V and 470 V in. Pulling a 300 V supply back up to 415 V means adding 115 V — a 38% lift on the incoming supply, with the series winding carrying roughly 83 kVA of the 300 kVA throughput. Below 300 V it runs out of range, and the answer is a wider-window build, not more kVA.

Response time

< 20 ms

At this rating the stabilizer is feeding a whole section of the floor, so < 20 ms determines whether one machine's inrush propagates into every other machine on the same board. That is the mechanism behind most "random" tripping complaints we are called out to.

Overload headroom

150% for 30 minutes

Direct-on-line starting draws six to eight times full-load current for a few seconds, and 150% for 30 minutes is the margin that absorbs it. At 300 kVA the practical constraint is usually the largest single motor rather than the total: size against that starting current, not against the sum of the nameplates.

Sizing Guide

When is 300 kVA the right choice?

300 kVA is the most common size for large integrated manufacturing floors that operate across two shifts. A typical stone-crushing plant or quarry processing unit with crushers, conveyors, dust collectors, and weighbridge systems draws 260–300 kVA at peak. Chemical process plants where multiple agitator motors, pumps, and heating elements run simultaneously also cluster at this rating. One important sizing note: if your load includes a significant proportion of variable frequency drives (VFDs), the regenerative braking current from multiple VFDs can momentarily push the actual drawn kVA above nameplate — specify 300 kVA rather than 250 kVA to maintain safe operating margins.

Before you order

Where 300 kVA goes in, and what the site needs

Typical installations

We supply 300 kVA most often into large manufacturing facilities, steel mills, automotive manufacturing and textile mills, alongside paper manufacturing and power distribution substations. What separates those sites is duty cycle rather than load. A rating that runs cool on single-shift work sits near the top of its thermal range on a continuous three-shift line, and that is the point at which oil cooling stops being optional.

Site preparation

At 1,200 kg this is forklift work, and the forklift has to be rated for 1,200 kg at the extended reach that placement requires. Confirm floor loading before it arrives — a ground-floor workshop slab is normally adequate, a mezzanine generally is not. Leave working clearance on the terminal side for cable entry and inspection. Sustained ambient above 45 °C, or an enclosed room without cross-ventilation, requires derating — send us the room conditions and we will confirm the rating still holds where you intend to put it.

Ready to specify?

Share your load profile. Get a firm proposal in 24 hours.

Send us your kVA requirement, supply voltage range, and site conditions. Our engineer will confirm whether this configuration is correct for your installation, or specify an alternative if needed. No distributors — direct from our factory in Hapur.

Submit load requirements