Servo Voltage Stabilizer

1000 kVA Servo Voltage Stabilizer

Ultra-high-capacity 1000 kVA servo voltage stabilizer for large power distribution and critical industrial operations. Engineered for maximum reliability with dual servo motor control and redundant safety systems.

Rating1000 kVA
Voltage415V AC, 3-Phase
Coolingboth air and oil cooled
Lead Time3–4 weeks

Ref. SVS-1000-3PH · Lead time 3–4 weeks · Made to order from Hapur

See full engineering specification & variants
1000 kVA Servo Voltage Stabilizer

Key Features

±1% voltage regulation
Dual servo motor control
Response time < 20 ms
Capacity: up to 150% for 30 minutes
ONAN with intelligent fan control
IP54 protection
Redundant protection circuits
Remote SCADA integration

Recommended For

Power Distribution Substations
Large Industrial Complexes
Semiconductor Manufacturing
Data Center Power Conditioning
Petrochemical Plants
Renewable Energy Integration

Specifications

SpecificationValue
Capacity1000 kVA
Input Voltage300V–470V, 3-Phase
Output Voltage415V ±1%
Frequency50/60 Hz
Response Time< 20 ms
Cooling Methodboth air and oil cooled
Weight3800 kg
Warranty3 years + extended support

Reading the specification

What these numbers mean for your installation

A datasheet tells you what the unit does. This is what each figure changes about how you specify, feed and site it — worked out for the 1000 kVA specifically, not the range in general.

Rated current

1,391 A per phase

At 415 V three-phase, 1000 kVA works out at roughly 1,391 A per phase. 1,391 A is a substation-scale connection. Cable is no longer sensible: this terminates on busduct, and the connection design — bar sizing, joint torque, thermal expansion allowance over the run — becomes a piece of engineering in its own right rather than a cable schedule. We supply the termination arrangement with the unit so the interface is settled before either side is built.

Correction window

300V–470V

The unit holds output at 415V ±1% anywhere between 300 V and 470 V in. Pulling a 300 V supply back up to 415 V means adding 115 V — a 38% lift on the incoming supply, with the series winding carrying roughly 277 kVA of the 1000 kVA throughput. Below 300 V it runs out of range, and the answer is a wider-window build, not more kVA.

Response time

< 20 ms

At this scale the stabilizer is effectively part of the incoming supply rather than a device hanging off it, and < 20 ms is what stops a disturbance anywhere in the plant from becoming a disturbance everywhere. Sites at this rating usually want the correction logged as well as performed — the remote monitoring option exists for exactly that.

Overload headroom

150% for 30 minutes

Direct-on-line starting draws six to eight times full-load current for a few seconds, and 150% for 30 minutes is the margin that absorbs it. At 1000 kVA the practical constraint is usually the largest single motor rather than the total: size against that starting current, not against the sum of the nameplates.

Sizing Guide

When is 1000 kVA the right choice?

1000 kVA is a plant-level rating, not a machine-level rating. It is typically specified when an entire factory block — compressors, heavy presses, conveyors, paint booths, and office loads — feeds from a single HT/LT transformer and the facility engineer wants a single point of voltage regulation before the main LT bus. At this size, dual servo motor control is essential: a single servo mechanism cannot physically respond fast enough across a full 1000 kVA window. Petrochemical process plants and semiconductor fabs also specify this rating because their equipment cannot tolerate even transient voltage events during critical batch cycles. SCADA integration is standard on this unit — your control room will see the stabilizer's input voltage, output voltage, load percentage, and fault log in real time.

Before you order

Where 1000 kVA goes in, and what the site needs

Typical installations

We supply 1000 kVA most often into power distribution substations, large industrial complexes, semiconductor manufacturing and data center power conditioning, alongside petrochemical plants and renewable energy integration. What separates those sites is duty cycle rather than load. A rating that runs cool on single-shift work sits near the top of its thermal range on a continuous three-shift line, and that is the point at which oil cooling stops being optional.

Site preparation

At 3,800 kg this is a crane lift onto an engineered foundation, and it needs a structural opinion rather than an assumption — over this footprint the point load, not the total mass, is what governs. Settle the lifting plan and access route at order stage; 3,800 kg cannot be repositioned once it is down. Leave working clearance on the terminal side for cable entry and inspection. Sustained ambient above 45 °C, or an enclosed room without cross-ventilation, requires derating — send us the room conditions and we will confirm the rating still holds where you intend to put it.